如何删除: "压降太大 - 修改供热/供冷区或供热/供冷面的参数"
| 产品 | InstalSystem 5 |
| 文章类型 | TIP&TRICK |
| 版本的最新内容 | 2022-04-21 |
问题说明
当系统中有压力损失过大的问题时,就会出现如下诊断信息:
- 压力损失太大 - 修改供热/供冷区或供热/供冷面的参数
当有如下情况时,就会显示这一错误信息:
- The number of 供热/供冷面 components specified by the user blocks the possibility of partitioning the 地面供热/供冷区 component.
- For the manual partitioning mode of the 地面供热/供冷区 component, the pressure drop in the 供热/供冷面 component belonging to the zone is exceeded.
Solution
Standard operations leading to the elimination of this error:
- Increase delta T in the loop in the 交互式辐射系统计算 window.

1. Change delta T in a loop. - Manually separate parts of the 供热/供冷区 component that cause a problem during automatic division (e.g. those having indentations for partition walls) and, if necessary, manually divide them into 供热/供冷面 components.
更多信息,见: Heating/cooling surface zone. - Increase the number of 供热/供冷面 components. This should be done in the 参数表 window of the 地面供热/供冷区 component in the 供热/供冷面的数量 field.

2. 供热/供冷面的数量 in the 地面供热/供冷区 component.