The supply temperature is selected from the <min,max> range specified in the heat source data. The calculations are performed with high precision using a temperature increment of 0.1 K. For each intermediate value of the supply temperature, complete calculations of the radiant heating installation are performed, where the variables are: pipe spacing, number of loops and temperature drop of the medium in the loop. First, the preferred spacing configurations are those for which, according to the settings in the Advanced Settings tab, the heating outputs fall within the 'Matching' range. Second priority is given to those classified as 'Moderately Mismatched'. Finally, if no spacing configurations allow for achieving the required heating output (within the entire permissible supply temperature range) within the specified tolerance, the remaining spacing options are considered. In such cases, the heating outputs obtained from the selected or all surfaces may be significantly too high or too low.
This process generates the so-called 'quality function', which is graphically represented as a polyline on 图形最佳化. 3. 控制回路. 4. 图形最佳化.
Next, the point with the best value of the quality function is selected (the highest on the 图形最佳化).). In the case where multiple temperatures have the same maximum value of the quality function (within a certain tolerance), the program chooses the lowest of them.
The shape of the quality function also depends on the selected variant of supply temperature optimization:
For the 热输出和压降 criterion, the parameters mainly affecting user comfort are considered, i.e., the possibility of achieving a lower floor temperature, but also theoretically the possibility of changing the floor covering.
For the 最小投资成本 criterion, in addition to the parameters influencing user comfort, investment costs are also taken into account. Hence, solutions that allow for larger pipe spacing and, for example, the use of a manifold with fewer circuits are preferred.
It is possible to obtain an identical supply temperature value for both optimization criteria, but most often the program will then select different values of pipe spacing. This results from the fact that the quality function for temperature behaves differently for the two criteria, although its maximum may occur at the same point. However, for the same value under the 最小投资成本 criterion, the program will select a larger spacing in order to reduce the total pipe length.
An error message may occur indicating that it is not possible to determine the supply temperature (e.g., if the required heating capacity is too high compared to the system’s capability). In such a case, the program adopts the maximum value defined for the given control circuit (source/mixing valve/mixing unit).