如何删除: "压降太大 - 修改供热/供冷区或供热/供冷面的参数"

来自HelpSystem
Dyst CN讨论 | 贡献2023年7月17日 (一) 13:33的版本 (建立内容为“<!-- case 272764--> <IS_HELP id="HS124"/> {{Article table |commercial_product1=InstalSystem 5 |p2 = |p3 = |p4 = |c…”的新页面)

(差异) ←上一版本 | 已核准修订 (差异) | 最后版本 (差异) | 下一版本→ (差异)
跳转到导航 跳转到搜索


产品 InstalSystem 5
文章类型 TIP&TRICK
版本的最新内容 2022-04-21


Problem description

Problems with excessive pressure loss in the system are identified by means of a diagnostics message:

  • 压力损失太大 - 修改供热/供冷区或供热/供冷面的参数.

The error message is displayed when:

  • The number of 供热/供冷面 components specified by the user blocks the possibility of partitioning the 地面供热/供冷区 component.
  • For the manual partitioning mode of the 地面供热/供冷区 component, the pressure drop in the 供热/供冷面 component belonging to the zone is exceeded.

Solution

Standard operations leading to the elimination of this error:

  • Increase delta T in the loop in the 交互式辐射系统计算 window.
    1. Change delta T in a loop.

  • Manually separate parts of the 供热/供冷区 component that cause a problem during automatic division (e.g. those having indentations for partition walls) and, if necessary, manually divide them into 供热/供冷面 components.
    更多信息,见: Heating/cooling surface zone.
  • Increase the number of 供热/供冷面 components. This should be done in the 参数表 window of the 地面供热/供冷区 component in the 供热/供冷面的数量 field.
    2. 供热/供冷面的数量 in the 地面供热/供冷区 component.