如何删除: "在循环回路外的热水管网中水量太多"

来自HelpSystem
Dyst CN讨论 | 贡献2022年8月15日 (一) 12:54的版本

跳转到导航 跳转到搜索


产品 InstalSystem 5
文章类型 提示和技巧
版本的最新内容 2022-03-18


问题说明

Problems with too high installation capacity not included in circulation are diagnosed by the program with a diagnostic message:
在循环回路外的热水管网中水量太多 (%s).

  • The problem may occur when the part of hot water installation not included in circulation has capacity higher than declared in 计算标准.
  • When the selection of the ring part is selected in on the 计算标准, this diagnostic can also include the ring parts. It is impossible to connect the circulation to the ring.

Solution

To eliminate the message, the hot water source must have a circulation input.

  • If a circulation installation already exists in the project, it should be extended to the farthest possible part of the installation (outside the ring).
    1. Add a circulation pipe-run.

  • If a 户用换热机组 is used, select a model with the circulation input option (declare the use of a circulation set in the data table) and draw the circulation installation on the residential side.
    2. Select the type of Flat station.

  • The value of the water capacity above which the message is generated is set in the field 允许的循环不到的部件中的水容量 on scope 计算标准 in the 一般参数 window.
    3. Increase the values in 允许的循环不到的部件中的水容量