如何删除: "超过最大空气流速"警告信息:修订间差异

来自HelpSystem
跳转到导航 跳转到搜索
第23行: 第23行:
*'''''<IS_TS id=errAirFlowSpeedOutOfRange/>'''''。
*'''''<IS_TS id=errAirFlowSpeedOutOfRange/>'''''。


==Solution==
==解决方法==
If a message about exceeding the vmax value in the ducts appears, the following steps can be taken to correct this issue:
如果风管中的风速有超过最大限值Vmax值的消息,可以采取以下步骤来更正此问题:


* select the duct types with larger diameters as default, for a specific location, in the ''<IS_TS id=rsDanogi/>''/''<IS_TS id=strInstalacjeWentylacyjneGdm/>''/''<IS_TS id=DaneInstalacjiRozprowadzajacejCzynnikGrzewczyChlodniczy/>'' window;
* ''<IS_TS id=rsDanogi/>''/''<IS_TS id=strInstalacjeWentylacyjneGdm/>''/''<IS_TS id=DaneInstalacjiRozprowadzajacejCzynnikGrzewczyChlodniczy/>'' 窗口,为特定位置,选择更大直径的风管类型作为默认设置。
* select the larger diameter type for individual ducts in the '' <IS_TS id=DataEditorTable/>'' after first selecting the ducts (a two-click on the diagnostic message selects the problematic ducts);  
* select the larger diameter type for individual ducts in the '' <IS_TS id=DataEditorTable/>'' after first selecting the ducts (a two-click on the diagnostic message selects the problematic ducts);  
* make the distribution with a greater number of ducts;
* make the distribution with a greater number of ducts;

2025年3月24日 (一) 16:24的版本


产品 InstalSystem 5
文章类型 提示和技巧
版本的最新内容 2025-01-10


问题说明

通风系统计算 范围进行项目的计算后,有可能会出现此问题,并在诊断 窗口中出现下面的警告消息:

  • 超过最大空气流速(%s m/s>%s m/s)

解决方法

如果风管中的风速有超过最大限值Vmax值的消息,可以采取以下步骤来更正此问题:

  • 一般参数/通风系统计算/默认类型和参数 窗口,为特定位置,选择更大直径的风管类型作为默认设置。
  • select the larger diameter type for individual ducts in the 参数表 after first selecting the ducts (a two-click on the diagnostic message selects the problematic ducts);
  • make the distribution with a greater number of ducts;
  • insert additional air diffusers/extractors;
  • increase the value in the 最大气流速度, V最大 box as default in the 一般参数/通风系统计算/默认类型和参数 window or in the 参数表 window for particular ducts.
    1. 一般参数/通风系统计算/默认类型和参数.

    2. Ventilation duct - 参数表.